MPL88-12 Handle MPL Series - For High Rate, Long Life Standby Use
Approx. Weight: | 26.4kg (58.2lbs) |
Dimensions: |
261L x 173W x200H x B5:224, I2:207TH (mm) 10.28L x 6.81W x7.87H x B5:8.82, I2:8.15TH (inch) |
MPL88-12 Handle MPL Series - For High Rate, Long Life Standby Use
Short Circuit Current: 2300 A
Internal Resistance: ≦4mΩ ( Fully Charged )
Operating Temperature Range:
Charge 0 C~50 C(32 F~122 F)
Discharge -20 C~60 C(-4 F~140 F)
Storage. -20 C~50 C(-4 F~122 F)
Container Material: Standard: PP( UL 94-HB) MPL88-12 Optional: Flame Retardant ABS(UL 94-V0) MPL88-12FR
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
Voltage : 12 V
Approx. Weight : 26.4kg (58.2lbs)
Dimensions : 261L x 173W x200H x B5:224, I2:207TH (mm)
10.28L x 6.81W x7.87H x B5:8.82, I2:8.15TH (inch)
Terminal : B5 (Fitting M6 bolt & nut) I2 is optional
Max Charge Current : 25.8 A
Application : Golf Cart, UPS, Telecom, Cable TV, Power station, Marine