FTB Series - Front Terminal Battery
FTB Series - Front Terminal Battery

FTB100-12 (gassing) FTB Series - Front Terminal Battery

Voltage: 12 V
Nominal Capacity 1(10Hr), 1(1Hr)
Approx. Weight 36.8kg (81.13lbs)
Dimensions 394 L x 110 W x287H x 287TH (mm)
15.51L x 4.33W x11.30 H x 11.30TH (inch)
Application: UPS, Telecom, Broadband, Electric Utility
Terminal: I2

Specification Download

FTB100-12 (gassing) FTB Series - Front Terminal Battery

• Absorbent Glass Mat technology for efficient gas recombination
• Front accessible terminal for ease of assembly
• Carry handles for ease of installation
• Strengthened rib design to maintain structural integrity
• Flame-arrestor is installed to ensure safety
• One-way self-resealing safety valve with gas collection system for long life guarantee

Internal Resistance: ≦3.5mΩ ( Fully Charged )


Operating Temperature Range:

 

Charge 0°C~40°C(32°F~104°F)

 Discharge -20°C~50°C(-4°F~122°F)

Storage. -20°C~40°C(-4°F~104°F)


Container Material:  Standard: ABS( UL 94-HB) FTB100-12  Optional: Flame Retardant ABS(UL 94-V0) FTB100-12FR


All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.

 

 

 

Voltage : 12 V

Nominal Capacity : 1(10Hr), 1(1Hr)

Approx. Weight : 36.8kg (81.13lbs)

Dimensions : 394 L x 110 W x287H x 287TH (mm)
                        15.51L x 4.33W x11.30 H x 11.30TH (inch)

Terminal : I2 (M6 Female Thread)

Max Discharge Current for 5 Sec :800 A (5 sec.)

Max Charge Current : 25 A

Application : UPS, Telecom, Broadband, Electric Utility